These
units are designed to provide cooling, heating, and pressurization
in one assembly. Although separate pressurization and
air conditioning units are still viable alternatives, they
are being used less and less as more efficient combination
units are sought out for new installations. Combining
the two systems into one unit has distinct advantages.
These advantages
include:
- Dehumidifying and pre-conditioning the pressurization air
before it enters
the
room prevents condensation and wide temperature swings,
- The unit
is completely pre-wired,
- Less wall
space is required than with a separate air conditioner and
pressurizer,
and,
- Installation
time is faster.
The
WCPX (explosion proof air conditioner)
and WHPX (explosion proof heat pump)
series are CSA (C/US) certified for hazardous
locations in sizes 1-1½ through 6 tons, and
are available up to 20 tons. In addition to the apropriate
Class I, Division markings, units may additionally be marked
with the US and Canadian Class I, Zone system upon request
(example: Class I, Zone 2, group IIB+H2).
-
The WCPX-G and WHPX-G
series is specifically designed for switchgear buildings,
MCC rooms, RIE buildings, control rooms, and similar buildings
whose interiors will be declassified to an ordinary (non-hazardous)
location by the pressurization and purge features of the
unit.
-
The WCPX-H and WHPX-H
series is specifically designed for analyzer shelters
and similar enclosures containing a source of flammable
gas, vapor, or liquid and having limited, or no release
of these materials under normal conditions (for more information,
refer to NFPA 496, chapter 9).
IEC
Zone 2 - The WCPF-G and
WCPF-H series are similar to the WCPX except
that they are designed for use in IEC Zone 2 hazardous areas.
Although they do not bear the CE mark or A.T.E.X. certification
as required for installation in the European Union, they are
intended for use in other countries that prefer the IEC methods
of protection. The WCPF-G and WCPF-H series are certified
to conform to Zone 2 requirements by Marc Climatic Controls
and all applicable Certificates of Conformity will be provided
for components. These air conditioners are not for installation
in North America.
The
VPAX series is specifically designed to provide
a safe, clean indoor environment for RIE and similar buildings
containing computers and other sensitive electronics. The
system provides Class I, Division 2 hazardous location positive
pressurization of 0.1” WC (min.) to prevent infiltration of
hazardous and corrosive gasses and reduce the classification
inside the building to an ordinary (non-hazardous) location.
Featuring
twin removable heating and cooling units
for full redundancy, the VPAX incorporates
cooling, heating, and dual pressurization with gas-phase air
filtration into a single system. The VPAX
is designed to allow for easy installation and maintenance.
The complete assembly is designed for installation on the
exterior of the building. Structural support underneath the
VPAX is required to be provided by the customer.
Only the control section with supply and return air openings
penetrates the building making for a minimal wall cutout.
To
protect sensitive equipment, make-up air for purge and pressurization
is scrubbed as it passes through particulate pre-filters,
carbon and/or potassium permanganate media cells, and final
filters to remove corrosive gasses and other pollutants.
A portion of the return air from the enclosed space is passed
through the filtration section of the system for continual
cleaning of the indoor atmosphere. Pressurization air
passes through the cooling and heating sections and is preconditioned
before entering the room.
In
compliance with NFPA 496, each pressurization blower provides
a purge of 60 feet per minute through one or two open doors
to maintain the nonhazardous classification of the indoor
space and prevent the entrance of hazardous and corrosive
gasses.
Standard VPAX
features include:
• Single-package
construction with fork-lift base and completely pre-wired
controls
for ease of installation,
• Class I, Division
2 design in the condenser (outdoor) and pressurization sections,
• Two independent
cooling and heating systems, separate thermostats and
humidistats,
and a 7-day timer to allow equal run time for each system,
• Dual pressurization
and dual purge in compliance with NFPA 496,
• Gas-phase air filtration
with chemical media cells and easy access for
removal and replacement,
• Alarm for loss
of room pressure,
• Corrosion protection
coatings on coils, compressors, copper tubing, and
other
exposed components,
• Urethane coated
galvanized steel cabinetry (stainless steel optional),
• Fresh air stack
with rain cap.
The
DCPX-CF series is a single packaged, fully
redundant cooling, heating, pressurizing and purge
system while incorporating a deep bed scrubber for gas-phase
air filtration into its design. The unit includes particulate
pre-filters, a carbon or potassium permanganate media bed,
re-filters, and final HEPA filters to remove corrosive gasses
and other pollutants.
The
system also provides positive pressurization to prevent infiltration
ofhazardous and corrosive gasses and reduce the classification
inside the building to an ordinary (non-hazardous) location.
Fresh
air stacks can be furnished in a guy-wire or free-standing
style and includes a rain cap with bird screen. Free-standing
stacks can be furnished in either a welded pipe design
or in a lighter weight, heavy gauge spiral pipe design.
Our free-standing stacks are made in 10 foot long (max.) sections
and with heavy, seal-welded flanges at both ends. The
free-standing stacks are P.E. Certified for:
- 130
MPH winds - Free-standing spiral pipe design, 27
foot tall.
- 150 MPH winds - Free-standing welded
pipe design, 27 foot tall.
Free-standing stacks must be properly
secured at the base with anchor bolts in a concrete foundation
or seal-welded to a structural steel support.
Packaged
units and split systems are available in much greater
cooling capacities. Systems are designed for Class I, Division
2 hazardous (classified) locations and to provide Type Z pressurization.
Chemical filtration and redundant blowers can also be incorporated
into the design. All systems are capable of a black
start.
Click on the photo
to view a larger image. |
| Download
a Brochure PDF by clicking on the link
below the photo. 
Adobe Acrobat is required to
view these documents.
If you do not have Adobe Acrobat installed please click
here. |
CSA
(C/US) CERTIFIED explosion proof pressurization units,
pressurizing units, room pressurizers, explosion proof
air conditioners, explosion proof air conditioning,
explosion proof heat pumps, explosion proof HVAC, hazardous
location air conditioners, hazardous duty air conditioners,
explosion proof heaters, explosion proof fans, ventilation
fans and other equipment for hazardous locations in
petrochemical, refining and offshore industries. |
|
|